fault detector
TCA
The TCA has been designed to detect, in MV networks, faults having triggered the line main breaker, whether is overhead or underground. Applications include the following:

· Secondary substations.
· Reclosers in overhead lines where location, insulation and service restoration logics are required.

For a reliable detection (signaling after the fault takes place) an overcurrent, absence of voltage and directional conditions must be present to avoid mistaken indications due to capacitive currents, inrush currents in line branches and connections from self-generators.
Protection functions
Fault detection DPF
Phase overcurrent 50/51
Neutral overcurrent 50N/51N
Sensitive neutral overcurrent 50Ns/51Ns
Directional phase overcurrent 67
Directional neutral overcurrent 67N
Phase overvoltage unit 59
Neutral overvoltage unit 59N
Voltage unit (presence/absence) 27
Fault locator
Fault isolation
Fault restoration automatic control
Additional functions
Time units with selectable curves (IEC and ANSI).
DIN rail mount.
Interfaces with measuring sensors.
Four (4) RJ45 inputs.
Twelve (12) digital inputs.
Six (6) digital outputs.
Nine (9) signaling Led´s.
Communications: 1 - RS232 / 2 - RJ45 - To SCADA (IEC-870-5-104)
Optical indicators.
Time synchronization.
Event recording.
Measurement recording.
Power quality.
Oscillography recording (COMTRADE 99).
Programmable logic.